Okaloosa County Water & Sewer System water quality
Fort Walton Beach, FL · serves 80,295 people (32,118 connections) · Groundwater · Local government · EPA ID FL1460506
Data: U.S. EPA · How we read the data · How we check it
Buys water from Okaloosa County Mid System (Crestview). Treated water bought from another system can carry that system's contaminants.
Summary
No federal limits exceeded in EPA data.
- PFAS
- Not detectedNone of 29 PFAS found above EPA's reporting limits in 16 samples (2023–2025).
- Lithium
- Above screening levelHighest result 24.6 ppb. EPA uses 10 ppb to decide what to study further. It is not a health limit, and there is no federal limit for lithium. About 1 in 4 systems tested were above it.
- Lead
- Below action level2.6 ppb (parts per billion) at the 90th percentile: 9 in 10 homes sampled were at or below it. Action level 15 ppb, falling to 10 ppb in Nov 2027. Monitoring period ending Dec 2023. Your home's pipes can make yours higher.
- Violations
- None health-basedNo health-based violations since 2016.
- Built before 1986, or not sure what your service line is made of? Check your service line and test your tap. Utility data can't show your pipes.
- Tested your own tap? Compare your result with these numbers. Moving? Compare this system with another.
- Read Okaloosa County Water & Sewer System's annual water quality report (Consumer Confidence Report). It lists every regulated contaminant tested and is usually on the utility's website or mailed with your bill, and you can also request it at (850) 651-7172. EPA: how to find it.
PFAS (“forever chemicals”)
EPA UCMR 5: 8 entry points tested Feb 2024 to Sep 2024. "Average" is the highest entry-point average (non-detects counted as zero), the way EPA compares UCMR 5 results to the limits. ppt = parts per trillion. These results do not determine compliance.
| Contaminant | Highest average |
|---|---|
| PFOA Not detected Limit 4 ppt | – |
| PFOS Not detected Limit 4 ppt | – |
| PFHxS Not detected Limit 10 ppt | – |
| PFNA Not detected Limit 10 ppt | – |
| HFPO-DA (GenX) Not detected Limit 10 ppt | – |
| Hazard Index (a combined score for PFHxS, PFNA, GenX and PFBS, where above 1 is over the limit) Not detected Limit 1 | – |
| PFBS Not detected Guideline 2,000 ppt | – |
| PFBA Not detected Guideline 6,000 ppt | – |
| PFHxA Not detected Guideline 3,000 ppt | – |
29 PFAS tested, 0 detected at least once. "Not detected" means below EPA's reporting limit (about 2 to 20 ppt depending on the chemical), not proven zero. PFAS not listed were not detected. The limits for PFHxS, PFNA, GenX and the Hazard Index were proposed for rescission in May 2026. That proposal is not final. Systems have until 2029 to meet the limits.
Lithium
Detected in 15 of 16 samples. Highest result 24.6 ppb. EPA's non-enforceable screening level is 10 ppb. Above screening level The screening level is how EPA decides what to study further, not a health limit. There is no federal limit for lithium and no filter is certified to remove it. About lithium.
Lead and copper
Latest 90th percentile: 2.6 ppb lead (Jan 2023 – Dec 2023). Below action level
Highest since 2016: 20 ppb (Dec 2017).
| Monitoring period | Lead (90th pct.) |
|---|---|
| Jan 2023 – Dec 2023 | 2.6 ppb |
| Jan 2020 – Dec 2020 | 8.3 ppb |
| Jan 2019 – Dec 2019 | 6.7 ppb |
Earlier results (9)
| Jul 2018 – Dec 2018 | 2.8 ppb |
| Jan 2018 – Jun 2018 | 2.3 ppb |
| Jan 2017 – Dec 2017 | 20 ppb |
| Jan 2014 – Dec 2014 | 2.7 ppb |
| Jan 2012 – Dec 2012 | 4.3 ppb |
| Jan 2010 – Dec 2010 | 6.8 ppb |
| Jan 2007 – Dec 2007 | 5.8 ppb |
| Jan 2002 – Dec 2004 | 7.1 ppb |
| Jan 2002 – Dec 2004 | 7.1 ppb |
Lead comes from pipes and fixtures, not the source water, so it varies home to home. The 90th percentile means 9 in 10 sampled homes were at or below it. More on lead.
Violations
Health-based violations mean a contaminant exceeded a limit or a required treatment step was missed. Monitoring and reporting violations mean required tests or reports were late or missing, so the water's quality during that time is unknown. The total includes every violation in EPA's records, most of them paperwork.
Earlier EPA testing (2013–2020)
| Contaminant | Highest | Guideline |
|---|---|---|
| Manganese | 23 ppb | 300 ppb |
| 1,4-Dioxane | 0.08 ppb | 0.35 ppb |
| Chromium-6 | 0.06 ppb | – |
| Strontium | 1.5 ppm | 1.5 ppm |
| Molybdenum | 1.5 ppb | 40 ppb |
Where it serves
Fort Walton Beach
ZIP codes the system reported serving: 32547, 32548, 32569, 32579
Nearby utilities
- Bagdad-Garcon Point Water System Milton · 29 mi · PFAS above limit
- Midway Water System, Inc. Gulf Breeze · 33 mi · PFAS above limit
- Emerald Coast Utilities Authority (ECUA) Pensacola · 34 mi · PFAS above limit
- Nas Pensacola / Corry Station Water System Pensacola · 34 mi · PFAS above limit
- Peoples Water Service Company Pensacola · 34 mi · PFAS above limit
- Pace Water System, Inc. Pace · 35 mi · PFAS above limit
Questions
Is Okaloosa County Water & Sewer System water safe to drink?
Okaloosa County Water & Sewer System has no health-based violations since 2016. EPA testing found no PFAS above the federal limits. Federal data can't tell you about your own pipes: lead comes from service lines and plumbing, so test your tap if your home was built before 1986. For the official word, read the utility's annual Consumer Confidence Report.
Does Okaloosa County Water & Sewer System water have PFAS?
EPA tested Okaloosa County Water & Sewer System for 29 PFAS between Feb 2024 and Sep 2024 and none were detected above the reporting limits (about 2 to 20 ppt depending on the chemical).
What is the lead level in Okaloosa County Water & Sewer System water?
The most recent 90th-percentile lead result for Okaloosa County Water & Sewer System is 2.6 ppb, for the period ending Dec 2023. The federal action level is 15 ppb, falling to 10 ppb in November 2027. The 90th percentile means 9 in 10 homes sampled were at or below this number. Individual homes can be higher.
Check these numbers yourself
Every figure on this page comes from public EPA records. You don't have to take our word for it:
- EPA's own report for FL1460506: violations, enforcement and inspections, straight from EPA.
- EPA UCMR 5 data: the PFAS and lithium results (search the file for PWSID FL1460506).
- EPA SDWIS download: the lead results, population and violation records we use.
- The utility's annual water quality report (Consumer Confidence Report): ask Okaloosa County Water & Sewer System at (850) 651-7172, or see EPA's guide to finding it.
Found something that doesn't match? Tell us and we'll check it against EPA's records. How we check our data.
Source: U.S. EPA drinking water records and PFAS testing (UCMR 5). How we read the data.