Tap Water Results

Is Palm Springs, FL tap water safe?

Supplied by Village of Palm Springs · serves 32,467 people (13,197 connections) · Groundwater · EPA ID FL4501058

Data: U.S. EPA · How we read the data · How we check it

Summary

PFAS above the 2024 federal limits. Systems have until 2029 to meet the PFAS limits.

Is it an emergency? No: PFAS limits are about years of exposure, not a glass of water, and nothing in EPA's data calls for you to stop drinking the water today. If your utility ever issues a boil-water or do-not-drink notice, follow it.

PFAS
Above limitPFOA, PFOS above the federal limit in EPA's 2023–2025 testing (PFOA 15.5 ppt vs a limit of 4 ppt, PFOS 38 ppt vs a limit of 4 ppt, where ppt = parts per trillion).
Lead
Below action level0.9 ppb (parts per billion) at the 90th percentile: 9 in 10 homes sampled were at or below it. Action level 15 ppb, falling to 10 ppb in Nov 2027. Monitoring period ending Dec 2023. Your home's pipes can make yours higher.
Violations
None health-basedNo health-based violations since 2016.
What you can do
  • Pregnant, or mixing baby formula with tap water? Babies drink more water for their size, so PFAS exposure matters more for them. Consider bottled water or a filter certified for PFAS for formula, and ask your doctor. Health effects.
  • To lower your PFAS exposure now, a home filter certified for PFAS reduction works (reverse osmosis, or activated carbon certified to NSF/ANSI 53 or 58). Filters for these results.
  • Built before 1986, or not sure what your service line is made of? Check your service line and test your tap. Utility data can't show your pipes.
  • Tested your own tap? Compare your result with these numbers. Moving? Compare this system with another.
  • Read Village of Palm Springs's annual water quality report (Consumer Confidence Report). It lists every regulated contaminant tested and is usually on the utility's website or mailed with your bill, and you can also request it at (561) 965-5770. EPA: how to find it.

PFAS (“forever chemicals”)

EPA UCMR 5: 2 entry points tested Mar 2024 to Sep 2024. "Average" is the highest entry-point average (non-detects counted as zero), the way EPA compares UCMR 5 results to the limits. ppt = parts per trillion. These results do not determine compliance.

ContaminantHighest averageHighest resultLimitStatus
PFOA
Above limit
Limit 4 ppt
15.5 ppt
3.88× the limit
16 ppt4 pptAbove limit
PFOS
Above limit
Limit 4 ppt
38 ppt
9.5× the limit
39 ppt4 pptAbove limit
PFHxS
Rounds to the limit
Limit 10 ppt
10.4 ppt
at the limit
11 ppt10 pptRounds to the limit
PFNA
Not detected
Limit 10 ppt
––10 pptNot detected
HFPO-DA (GenX)
Not detected
Limit 10 ppt
––10 pptNot detected
Hazard Index (a combined score for PFHxS, PFNA, GenX and PFBS, where above 1 is over the limit)
Rounds to the limit
Limit 1
1.051.111Rounds to the limit
PFBS
Detected, below limit
Guideline 2,000 ppt
15.5 ppt16 ppt2,000 ppt guidelineDetected, below limit
PFBA
Detected, below limit
Guideline 6,000 ppt
6.05 ppt7.1 ppt6,000 ppt guidelineDetected, below limit
PFHxA
Detected, below limit
Guideline 3,000 ppt
8.85 ppt10 ppt3,000 ppt guidelineDetected, below limit
PFPeA
Detected, no limit
9.8 ppt10 pptnoneDetected, no limit
PFHpA
Detected, no limit
5.85 ppt6.5 pptnoneDetected, no limit

Why "rounds to the limit"? the PFHxS average (10.4 ppt) and the Hazard Index (1.05) are slightly above the number on paper, but EPA compares results after rounding to the limit's precision (4.4 ppt rounds to 4), so they meet the limit as EPA applies it. Close enough to the limit to be worth watching.

For context: the PFOA average is higher than at 98% of the Florida systems EPA tested and the PFOS average is higher than at 98% of the Florida systems EPA tested.

29 PFAS tested, 8 detected at least once. "Not detected" means below EPA's reporting limit (about 2 to 20 ppt depending on the chemical), not proven zero. PFAS not listed were not detected. The limits for PFHxS, PFNA, GenX and the Hazard Index were proposed for rescission in May 2026. That proposal is not final. Systems have until 2029 to meet the limits.

Lithium

Not detected in 4 samples (reporting limit 9 ppb). About lithium.

Lead and copper

Latest 90th percentile: 0.9 ppb lead (Jan 2023 – Dec 2023). Below action level

Highest since 2016: 1.3 ppb (Dec 2020).

Monitoring periodLead (90th pct.)
Jan 2023 – Dec 20230.9 ppb
Jan 2020 – Dec 20201.3 ppb
Jan 2017 – Dec 20170.7 ppb
Earlier results (9)
Jan 2014 – Dec 20141.5 ppb
Jan 2011 – Dec 20111.9 ppb
Jan 2009 – Dec 20091.1 ppb
Jul 2008 – Dec 20081.4 ppb
Jan 2008 – Jun 20082.3 ppb
Jan 2007 – Dec 20074.6 ppb
Jan 2006 – Jun 20061 ppb
Jan 2002 – Dec 20020 ppb
Jan 1999 – Dec 19991 ppb

Lead comes from pipes and fixtures, not the source water, so it varies home to home. The 90th percentile means 9 in 10 sampled homes were at or below it. More on lead.

Violations

0
Health-based since 2016
4
Monitoring/reporting since 2016
0
Health-based unresolved now (plus 1 paperwork)
12
Total ever recorded, incl. paperwork

Health-based violations mean a contaminant exceeded a limit or a required treatment step was missed. Monitoring and reporting violations mean required tests or reports were late or missing, so the water's quality during that time is unknown. The total includes every violation in EPA's records, most of them paperwork.

Earlier EPA testing (2013–2020)

ContaminantHighestGuidelineDetectedTested
Manganese4.9 ppb300 ppb2 of 4UCMR 4 (2020)
Vanadium1 ppb21 ppb6 of 6UCMR 3 (2014)
1,4-Dioxane0.11 ppb0.35 ppb1 of 4UCMR 3 (2014)
Chromium-60.54 ppb–8 of 8UCMR 3 (2014)
Chlorate760 ppb210 ppb8 of 8UCMR 3 (2014)
Strontium0.7 ppm1.5 ppm6 of 6UCMR 3 (2014)

Where it serves

Palm Springs

ZIP codes the system reported serving: 33406, 33415, 33461

Nearby utilities

Questions

Is Palm Springs tap water safe to drink?

Most of Palm Springs gets its water from Village of Palm Springs. Village of Palm Springs has no health-based violations since 2016. EPA testing found PFAS above the 2024 federal limits, which systems must meet by 2029. Federal data can't tell you about your own pipes: lead comes from service lines and plumbing, so test your tap if your home was built before 1986. For the official word, read the utility's annual Consumer Confidence Report.

Does Palm Springs water have PFAS?

Yes. EPA's 2023–2025 testing of Village of Palm Springs found 8 PFAS at least once. The highest entry-point averages were above the federal limit for PFOA and PFOS: PFOA 15.5 ppt, PFOS 38 ppt (limit 4 ppt for PFOA and PFOS, 10 ppt for the others).

What is the lead level in Palm Springs water?

The most recent 90th-percentile lead result for Village of Palm Springs is 0.9 ppb, for the period ending Dec 2023. The federal action level is 15 ppb, falling to 10 ppb in November 2027. The 90th percentile means 9 in 10 homes sampled were at or below this number. Individual homes can be higher.

Check these numbers yourself

Every figure on this page comes from public EPA records. You don't have to take our word for it:

Found something that doesn't match? Tell us and we'll check it against EPA's records. How we check our data.

Source: U.S. EPA drinking water records and PFAS testing (UCMR 5). How we read the data.