Carroll County Water System water quality
Carrollton, GA · serves 51,592 people (19,839 connections) · Surface water · Local government · EPA ID GA0450001
Data: U.S. EPA · How we read the data · How we check it
Buys water from Carrollton Water System, Bowdon Water System, Heard County Water Authority, Paulding County Water System, Haralson County Water Authority, Douglasville-Douglas County Water & Sewer Authority. Treated water bought from another system can carry that system's contaminants.
Summary
No federal limits exceeded in EPA data.
- PFAS
- Not detectedNone of 29 PFAS found above EPA's reporting limits in 10 samples (2023–2025).
- Lead
- Below action level7 ppb (parts per billion) at the 90th percentile: 9 in 10 homes sampled were at or below it. Action level 15 ppb, falling to 10 ppb in Nov 2027. Monitoring period ending Dec 2025. Your home's pipes can make yours higher.
- Violations
- None health-basedNo health-based violations since 2016.
- Built before 1986, or not sure what your service line is made of? Check your service line and test your tap. Utility data can't show your pipes.
- Tested your own tap? Compare your result with these numbers. Moving? Compare this system with another.
- Read Carroll County Water System's annual water quality report (Consumer Confidence Report). It lists every regulated contaminant tested and is usually on the utility's website or mailed with your bill, and you can also request it at (770) 832-1277. EPA: how to find it.
PFAS (“forever chemicals”)
EPA UCMR 5: 4 entry points tested Mar 2024 to Dec 2024. "Average" is the highest entry-point average (non-detects counted as zero), the way EPA compares UCMR 5 results to the limits. ppt = parts per trillion. These results do not determine compliance.
| Contaminant | Highest average |
|---|---|
| PFOA Not detected Limit 4 ppt | – |
| PFOS Not detected Limit 4 ppt | – |
| PFHxS Not detected Limit 10 ppt | – |
| PFNA Not detected Limit 10 ppt | – |
| HFPO-DA (GenX) Not detected Limit 10 ppt | – |
| Hazard Index (a combined score for PFHxS, PFNA, GenX and PFBS, where above 1 is over the limit) Not detected Limit 1 | – |
| PFBS Not detected Guideline 2,000 ppt | – |
| PFBA Not detected Guideline 6,000 ppt | – |
| PFHxA Not detected Guideline 3,000 ppt | – |
29 PFAS tested, 0 detected at least once. "Not detected" means below EPA's reporting limit (about 2 to 20 ppt depending on the chemical), not proven zero. PFAS not listed were not detected. The limits for PFHxS, PFNA, GenX and the Hazard Index were proposed for rescission in May 2026. That proposal is not final. Systems have until 2029 to meet the limits.
Lithium
Not detected in 10 samples (reporting limit 9 ppb). About lithium.
Lead and copper
Latest 90th percentile: 7 ppb lead (Jan 2023 – Dec 2025). Below action level
| Monitoring period | Lead (90th pct.) |
|---|---|
| Jan 2023 – Dec 2025 | 7 ppb |
| Jan 2020 – Dec 2022 | 1.8 ppb |
| Jan 2017 – Dec 2019 | 1.7 ppb |
Earlier results (9)
| Jan 2015 – Dec 2017 | 1.6 ppb |
| Jan 2013 – Dec 2015 | 2.5 ppb |
| Jan 2012 – Dec 2014 | 2.5 ppb |
| Jan 2010 – Dec 2012 | 3.6 ppb |
| Jan 2007 – Dec 2009 | 5.2 ppb |
| Jan 2004 – Dec 2006 | 3.3 ppb |
| Jan 2004 – Dec 2004 | 3.3 ppb |
| Jan 2003 – Dec 2003 | 8.6 ppb |
| Jan 2002 – Dec 2002 | 6.1 ppb |
Lead comes from pipes and fixtures, not the source water, so it varies home to home. The 90th percentile means 9 in 10 sampled homes were at or below it. More on lead.
Violations
Health-based violations mean a contaminant exceeded a limit or a required treatment step was missed. Monitoring and reporting violations mean required tests or reports were late or missing, so the water's quality during that time is unknown. The total includes every violation in EPA's records, most of them paperwork.
Earlier EPA testing (2013–2020)
| Contaminant | Highest | Guideline |
|---|---|---|
| Manganese | 127 ppb | 300 ppb |
| Chlorate | 450 ppb | 210 ppb |
| Strontium | 1.3 ppm | 1.5 ppm |
| Chromium-6 | 1.3 ppb | – |
| Vanadium | 3.1 ppb | 21 ppb |
Where it serves
ZIP codes the system reported serving: 30108, 30109, 30110, 30112, 30116, 30117, 30150, 30170, 30179, 30180, 30182, 30185
Questions
Is Carroll County Water System water safe to drink?
Carroll County Water System has no health-based violations since 2016. EPA testing found no PFAS above the federal limits. Federal data can't tell you about your own pipes: lead comes from service lines and plumbing, so test your tap if your home was built before 1986. For the official word, read the utility's annual Consumer Confidence Report.
Does Carroll County Water System water have PFAS?
EPA tested Carroll County Water System for 29 PFAS between Mar 2024 and Dec 2024 and none were detected above the reporting limits (about 2 to 20 ppt depending on the chemical).
What is the lead level in Carroll County Water System water?
The most recent 90th-percentile lead result for Carroll County Water System is 7 ppb, for the period ending Dec 2025. The federal action level is 15 ppb, falling to 10 ppb in November 2027. The 90th percentile means 9 in 10 homes sampled were at or below this number. Individual homes can be higher.
Check these numbers yourself
Every figure on this page comes from public EPA records. You don't have to take our word for it:
- EPA's own report for GA0450001: violations, enforcement and inspections, straight from EPA.
- EPA UCMR 5 data: the PFAS and lithium results (search the file for PWSID GA0450001).
- EPA SDWIS download: the lead results, population and violation records we use.
- The utility's annual water quality report (Consumer Confidence Report): ask Carroll County Water System at (770) 832-1277, or see EPA's guide to finding it.
Found something that doesn't match? Tell us and we'll check it against EPA's records. How we check our data.
Source: U.S. EPA drinking water records and PFAS testing (UCMR 5). How we read the data.