Tap Water Results

Savannah-I & D Water System water quality

Port Wentworth, GA · serves 10,500 people (1,967 connections) · Surface water · Local government · EPA ID GA0510004

Data: U.S. EPA · How we read the data · How we check it

Summary

PFAS above the 2024 federal limits. Systems have until 2029 to meet the PFAS limits.

Is it an emergency? No: PFAS limits are about years of exposure, not a glass of water, and nothing in EPA's data calls for you to stop drinking the water today. If your utility ever issues a boil-water or do-not-drink notice, follow it.

PFAS
Above limitPFOA above the federal limit in EPA's 2023–2025 testing (PFOA 5.1 ppt vs a limit of 4 ppt, where ppt = parts per trillion).
Lead
Below action level6.4 ppb (parts per billion) at the 90th percentile: 9 in 10 homes sampled were at or below it. Action level 15 ppb, falling to 10 ppb in Nov 2027. Monitoring period ending Dec 2023. Your home's pipes can make yours higher.
Violations
Resolved2 health-based violations since 2016, most recently Aug 2025. 2 required an urgent public notice within 24 hours (the kind behind boil-water notices), most recently Aug 2025. What to do if you get a notice.
What you can do

PFAS (“forever chemicals”)

EPA UCMR 5: 1 entry point tested Apr 2024 to Jan 2025. "Average" is the highest entry-point average (non-detects counted as zero), the way EPA compares UCMR 5 results to the limits. ppt = parts per trillion. These results do not determine compliance.

ContaminantHighest averageHighest resultLimitStatus
PFOA
Above limit
Limit 4 ppt
5.1 ppt
1.28× the limit
5.5 ppt4 pptAbove limit
PFOS
One sample above limit
Limit 4 ppt
3.6 ppt
90% of the limit
5.2 ppt4 pptOne sample above limit
PFHxS
Not detected
Limit 10 ppt
––10 pptNot detected
PFNA
Not detected
Limit 10 ppt
––10 pptNot detected
HFPO-DA (GenX)
Not detected
Limit 10 ppt
––10 pptNot detected
Hazard Index (a combined score for PFHxS, PFNA, GenX and PFBS, where above 1 is over the limit)
Detected, below limit
Limit 1
0.00190.00211Detected, below limit
PFBS
Detected, below limit
Guideline 2,000 ppt
3.85 ppt4.1 ppt2,000 ppt guidelineDetected, below limit
PFBA
Not detected
Guideline 6,000 ppt
––6,000 ppt guidelineNot detected
PFHxA
Not detected
Guideline 3,000 ppt
––3,000 ppt guidelineNot detected
PFPeA
Detected, no limit
0.8 ppt3.2 pptnoneDetected, no limit

For context: the PFOA average is higher than at 92% of the Georgia systems EPA tested.

29 PFAS tested, 4 detected at least once. "Not detected" means below EPA's reporting limit (about 2 to 20 ppt depending on the chemical), not proven zero. PFAS not listed were not detected. The limits for PFHxS, PFNA, GenX and the Hazard Index were proposed for rescission in May 2026. That proposal is not final. Systems have until 2029 to meet the limits.

Lithium

Not detected in 4 samples (reporting limit 9 ppb). About lithium.

Lead and copper

Latest 90th percentile: 6.4 ppb lead (Jan 2021 – Dec 2023). Below action level

Highest since 2016: 9.6 ppb (Dec 2020).

Monitoring periodLead (90th pct.)
Jan 2021 – Dec 20236.4 ppb
Jan 2018 – Dec 20209.6 ppb
Jan 2015 – Dec 20172.8 ppb
Earlier results (9)
Jan 2012 – Dec 20142.5 ppb
Jan 2011 – Dec 20132.7 ppb
Jan 2008 – Dec 20103.3 ppb
Jan 2005 – Dec 20073.2 ppb
Jan 2004 – Dec 20044.7 ppb
Jan 2003 – Dec 20034.3 ppb
Jan 2002 – Dec 20027.1 ppb
Jan 2001 – Jun 200113 ppb
Jul 2000 – Dec 20009.58 ppb

Lead comes from pipes and fixtures, not the source water, so it varies home to home. The 90th percentile means 9 in 10 sampled homes were at or below it. More on lead.

Violations

2
Health-based since 2016
0
Monitoring/reporting since 2016
0
Health-based unresolved now
22
Total ever recorded, incl. paperwork
WhenWhat happenedStatus
May 2025 – Aug 2025
2 times
The water was cloudier than allowed at least once. Cloudiness can shield germs from disinfection.
Urgent public notice required What that means
EPA record: Interim Enhanced Surface Water Treatment Rule · Single Turbidity Exceed (Enhanced SWTR) · measured 1.99 ntu (limit )
Archived
Archived

Health-based violations mean a contaminant exceeded a limit or a required treatment step was missed. Monitoring and reporting violations mean required tests or reports were late or missing, so the water's quality during that time is unknown. The total includes every violation in EPA's records, most of them paperwork.

Earlier EPA testing (2013–2020)

ContaminantHighestGuidelineDetectedTested
Manganese11 ppb300 ppb4 of 4UCMR 4 (2020)
Chromium-60.11 ppb–5 of 8UCMR 3 (2014)
Strontium0.05 ppm1.5 ppm8 of 8UCMR 3 (2014)
1,4-Dioxane0.36 ppb0.35 ppb2 of 4UCMR 3 (2014)
Vanadium0.7 ppb21 ppb8 of 8UCMR 3 (2014)
Chlorate29 ppb210 ppb1 of 8UCMR 3 (2014)

Where it serves

Port Wentworth, Garden City

ZIP codes the system reported serving: 31402, 31407, 31408, 31421

Nearby utilities

Questions

Is Savannah-I & D Water System water safe to drink?

Savannah-I & D Water System had 2 health-based violations since 2016, all since resolved. EPA testing found PFAS above the 2024 federal limits, which systems must meet by 2029. Federal data can't tell you about your own pipes: lead comes from service lines and plumbing, so test your tap if your home was built before 1986. For the official word, read the utility's annual Consumer Confidence Report.

Does Savannah-I & D Water System water have PFAS?

Yes. EPA's 2023–2025 testing of Savannah-I & D Water System found 4 PFAS at least once. The highest entry-point averages were above the federal limit for PFOA: PFOA 5.1 ppt (limit 4 ppt for PFOA and PFOS, 10 ppt for the others).

What is the lead level in Savannah-I & D Water System water?

The most recent 90th-percentile lead result for Savannah-I & D Water System is 6.4 ppb, for the period ending Dec 2023. The federal action level is 15 ppb, falling to 10 ppb in November 2027. The 90th percentile means 9 in 10 homes sampled were at or below this number. Individual homes can be higher.

Check these numbers yourself

Every figure on this page comes from public EPA records. You don't have to take our word for it:

Found something that doesn't match? Tell us and we'll check it against EPA's records. How we check our data.

Source: U.S. EPA drinking water records and PFAS testing (UCMR 5). How we read the data.