Is Taylor, MI tap water safe?
Supplied by Taylor Water System · serves 63,409 people (21,238 connections) · Purchased surface water · EPA ID MI0006545
Data: U.S. EPA · How we read the data · How we check it
Buys water from Great Lakes Water Authority. Treated water bought from another system can carry that system's contaminants.
Summary
No federal limits exceeded in EPA data. Some contaminants were detected below the limits.
- PFAS
- Not detectedNone of 29 PFAS found above EPA's reporting limits in 4 samples (2023–2025).
- Lead
- Near 2027 action level10.7 ppb (parts per billion) at the 90th percentile: 9 in 10 homes sampled were at or below it. Action level 15 ppb, falling to 10 ppb in Nov 2027. Monitoring period ending Jun 2026. Your home's pipes can make yours higher.
- Violations
- Resolved1 health-based violation since 2016, most recently Nov 2025.
- Built before 1986, or not sure what your service line is made of? Check your service line and test your tap. Utility data can't show your pipes.
- Want to reduce what was found? Filters for these results.
- Tested your own tap? Compare your result with these numbers. Moving? Compare this system with another.
- Read Taylor Water System's annual water quality report (Consumer Confidence Report). It lists every regulated contaminant tested and is usually on the utility's website or mailed with your bill, and you can also request it at (734) 374-1427. EPA: how to find it.
PFAS (“forever chemicals”)
EPA UCMR 5: 1 entry point tested Sep 2023 to Jun 2024. "Average" is the highest entry-point average (non-detects counted as zero), the way EPA compares UCMR 5 results to the limits. ppt = parts per trillion. These results do not determine compliance.
| Contaminant | Highest average |
|---|---|
| PFOA Not detected Limit 4 ppt | – |
| PFOS Not detected Limit 4 ppt | – |
| PFHxS Not detected Limit 10 ppt | – |
| PFNA Not detected Limit 10 ppt | – |
| HFPO-DA (GenX) Not detected Limit 10 ppt | – |
| Hazard Index (a combined score for PFHxS, PFNA, GenX and PFBS, where above 1 is over the limit) Not detected Limit 1 | – |
| PFBS Not detected Guideline 2,000 ppt | – |
| PFBA Not detected Guideline 6,000 ppt | – |
| PFHxA Not detected Guideline 3,000 ppt | – |
Michigan has its own PFAS limits. PFNA 6 ppt (this system's highest average: not detected), PFOA 8 ppt (this system's highest average: not detected), PFHxA 400000 ppt (this system's highest average: not detected), PFOS 16 ppt (this system's highest average: not detected), PFHxS 51 ppt (this system's highest average: not detected), PFBS 420 ppt (this system's highest average: not detected), HFPO-DA 370 ppt (this system's highest average: not detected). State compliance is judged on the state's own sampling, so ask the utility or the state program whether it meets them.
29 PFAS tested, 0 detected at least once. "Not detected" means below EPA's reporting limit (about 2 to 20 ppt depending on the chemical), not proven zero. PFAS not listed were not detected. The limits for PFHxS, PFNA, GenX and the Hazard Index were proposed for rescission in May 2026. That proposal is not final. Systems have until 2029 to meet the limits.
Lithium
Not detected in 4 samples (reporting limit 9 ppb). About lithium.
Lead and copper
Latest 90th percentile: 10.7 ppb lead (Jan 2026 – Jun 2026). Near 2027 action level
Highest since 2016: 16.3 ppb (Dec 2025).
| Monitoring period | Lead (90th pct.) |
|---|---|
| Jan 2026 – Jun 2026 | 10.7 ppb |
| Jan 2025 – Dec 2025 | 16.3 ppb |
| Jan 2024 – Dec 2024 | 12.7 ppb |
Earlier results (9)
| Jan 2023 – Dec 2023 | 8.3 ppb |
| Jan 2022 – Dec 2022 | 12.8 ppb |
| Jan 2021 – Dec 2021 | 10.7 ppb |
| Jan 2020 – Dec 2020 | 8.08 ppb |
| Jan 2019 – Dec 2019 | 10.9 ppb |
| Jan 2015 – Dec 2017 | 5.59 ppb |
| Jan 2012 – Dec 2014 | 3.4 ppb |
| Jan 2009 – Dec 2011 | 8.3 ppb |
| Jan 2006 – Dec 2008 | 5 ppb |
Lead comes from pipes and fixtures, not the source water, so it varies home to home. The 90th percentile means 9 in 10 sampled homes were at or below it. More on lead.
Violations
| When | What happened |
|---|---|
| Nov 2025 | After high lead results, the system did not give customers the required information about lead. EPA record: Lead and Copper Rule · Public Education (limit TT ) Resolved |
Health-based violations mean a contaminant exceeded a limit or a required treatment step was missed. Monitoring and reporting violations mean required tests or reports were late or missing, so the water's quality during that time is unknown. The total includes every violation in EPA's records, most of them paperwork.
Earlier EPA testing (2013–2020)
| Contaminant | Highest | Guideline |
|---|---|---|
| Manganese | 21.6 ppb | 300 ppb |
| Vanadium | 0.53 ppb | 21 ppb |
| Strontium | 0.12 ppm | 1.5 ppm |
| Chromium-6 | 0.11 ppb | – |
Where it serves
Taylor
ZIP codes the system reported serving: 48180
Nearby utilities
- Dearborn Water System Dearborn · 7 mi
- Dearborn Heights Water System Dearborn Heights · 8 mi
- Canton Township Water System Canton charter · 13 mi
- Livonia Water System Livonia · 13 mi
- City of Detroit Detroit · 14 mi
- Southfield Water System Southfield · 17 mi
Questions
Is Taylor tap water safe to drink?
Most of Taylor gets its water from Taylor Water System. Taylor Water System had 1 health-based violation since 2016, all since resolved. EPA testing found no PFAS above the federal limits. Federal data can't tell you about your own pipes: lead comes from service lines and plumbing, so test your tap if your home was built before 1986. For the official word, read the utility's annual Consumer Confidence Report.
Does Taylor water have PFAS?
EPA tested Taylor Water System for 29 PFAS between Sep 2023 and Jun 2024 and none were detected above the reporting limits (about 2 to 20 ppt depending on the chemical).
What is the lead level in Taylor water?
The most recent 90th-percentile lead result for Taylor Water System is 10.7 ppb, for the period ending Jun 2026. The federal action level is 15 ppb, falling to 10 ppb in November 2027. The 90th percentile means 9 in 10 homes sampled were at or below this number. Individual homes can be higher.
Check these numbers yourself
Every figure on this page comes from public EPA records. You don't have to take our word for it:
- EPA's own report for MI0006545: violations, enforcement and inspections, straight from EPA.
- EPA UCMR 5 data: the PFAS and lithium results (search the file for PWSID MI0006545).
- EPA SDWIS download: the lead results, population and violation records we use.
- The utility's annual water quality report (Consumer Confidence Report): ask Taylor Water System at (734) 374-1427, or see EPA's guide to finding it.
Found something that doesn't match? Tell us and we'll check it against EPA's records. How we check our data.
Source: U.S. EPA drinking water records and PFAS testing (UCMR 5). How we read the data.