Tap Water Results

South Granville Water&sewer Authority water quality

Butner, NC · serves 18,555 people (5,454 connections) · Surface water · Local government · EPA ID NC0239107

Data: U.S. EPA · How we read the data · How we check it

Summary

PFAS above the 2024 federal limits. Systems have until 2029 to meet the PFAS limits.

Is it an emergency? No: PFAS limits are about years of exposure, not a glass of water, and nothing in EPA's data calls for you to stop drinking the water today. If your utility ever issues a boil-water or do-not-drink notice, follow it.

PFAS
Above limitPFOA, PFOS above the federal limit in EPA's 2023–2025 testing (PFOA 6 ppt vs a limit of 4 ppt, PFOS 10.5 ppt vs a limit of 4 ppt, where ppt = parts per trillion).
Lead
Below action level3 ppb (parts per billion) at the 90th percentile: 9 in 10 homes sampled were at or below it. Action level 15 ppb, falling to 10 ppb in Nov 2027. Monitoring period ending Dec 2025. Your home's pipes can make yours higher.
Violations
Resolved7 health-based violations since 2016, most recently Jul 2017. One required an urgent public notice within 24 hours (the kind behind boil-water notices), most recently Oct 2016. What to do if you get a notice.
What you can do

PFAS (“forever chemicals”)

EPA UCMR 5: 1 entry point tested May 2023 to Feb 2024. "Average" is the highest entry-point average (non-detects counted as zero), the way EPA compares UCMR 5 results to the limits. ppt = parts per trillion. These results do not determine compliance.

ContaminantHighest averageHighest resultLimitStatus
PFOA
Above limit
Limit 4 ppt
6 ppt
1.5× the limit
11 ppt4 pptAbove limit
PFOS
Above limit
Limit 4 ppt
10.5 ppt
2.63× the limit
19 ppt4 pptAbove limit
PFHxS
Not detected
Limit 10 ppt
––10 pptNot detected
PFNA
Not detected
Limit 10 ppt
––10 pptNot detected
HFPO-DA (GenX)
Not detected
Limit 10 ppt
––10 pptNot detected
Hazard Index (a combined score for PFHxS, PFNA, GenX and PFBS, where above 1 is over the limit)
Not detected
Limit 1
––1Not detected
PFBS
Not detected
Guideline 2,000 ppt
––2,000 ppt guidelineNot detected
PFBA
Not detected
Guideline 6,000 ppt
––6,000 ppt guidelineNot detected
PFHxA
Not detected
Guideline 3,000 ppt
––3,000 ppt guidelineNot detected

For context: the PFOA average is higher than at 90% of the North Carolina systems EPA tested and the PFOS average is higher than at 92% of the North Carolina systems EPA tested.

29 PFAS tested, 2 detected at least once. "Not detected" means below EPA's reporting limit (about 2 to 20 ppt depending on the chemical), not proven zero. PFAS not listed were not detected. The limits for PFHxS, PFNA, GenX and the Hazard Index were proposed for rescission in May 2026. That proposal is not final. Systems have until 2029 to meet the limits.

Lithium

Not detected in 4 samples (reporting limit 9 ppb). About lithium.

Lead and copper

Latest 90th percentile: 3 ppb lead (Jan 2023 – Dec 2025). Below action level

Highest since 2016: 5 ppb (Dec 2019).

Monitoring periodLead (90th pct.)
Jan 2023 – Dec 20253 ppb
Jan 2021 – Jun 20210 ppb
Jul 2020 – Dec 20200 ppb
Earlier results (9)
Jan 2020 – Jun 20200 ppb
Jul 2019 – Dec 20195 ppb
Jan 2017 – Dec 20192 ppb
Jan 2019 – Jun 20190 ppb
Jul 2018 – Dec 20180 ppb
Jan 2018 – Jun 20180 ppb
Jul 2017 – Dec 20170 ppb
Jan 2014 – Dec 20160 ppb
Jan 2011 – Dec 20130 ppb

Lead comes from pipes and fixtures, not the source water, so it varies home to home. The 90th percentile means 9 in 10 sampled homes were at or below it. More on lead.

Violations

7
Health-based since 2016
0
Monitoring/reporting since 2016
0
Health-based unresolved now
42
Total ever recorded, incl. paperwork
WhenWhat happenedStatus
Apr 2017 – Jul 2017
2 times
The running annual average for TTHM was above the legal limit.
EPA record: TTHM · Maximum Contaminant Level Violation, Average · measured 0.09 mg/l (limit 0.080 mg/L)
Resolved
Resolved
Oct 2016 – Jul 2017
4 times
The running annual average for Total Haloacetic Acids (HAA5) was above the legal limit.
EPA record: Total Haloacetic Acids (HAA5) · Maximum Contaminant Level Violation, Average · measured 0.069 mg/l (limit 0.060 mg/L)
Resolved
Resolved
Oct 2016The water was cloudier than allowed at least once. Cloudiness can shield germs from disinfection.
Urgent public notice required What that means
EPA record: Interim Enhanced Surface Water Treatment Rule · Single Turbidity Exceed (Enhanced SWTR) (limit )
Resolved
Resolved

Health-based violations mean a contaminant exceeded a limit or a required treatment step was missed. Monitoring and reporting violations mean required tests or reports were late or missing, so the water's quality during that time is unknown. The total includes every violation in EPA's records, most of them paperwork.

Earlier EPA testing (2013–2020)

ContaminantHighestGuidelineDetectedTested
Manganese29.6 ppb300 ppb4 of 4UCMR 4 (2019)
Chromium-60.41 ppb–8 of 8UCMR 3 (2015)
Chlorate310 ppb210 ppb8 of 8UCMR 3 (2015)
Strontium0.035 ppm1.5 ppm8 of 8UCMR 3 (2015)

Where it serves

Butner

ZIP codes the system reported serving: 27509, 27522, 27525, 27581

Nearby utilities

Questions

Is South Granville Water&sewer Authority water safe to drink?

South Granville Water&sewer Authority had 7 health-based violations since 2016, all since resolved. EPA testing found PFAS above the 2024 federal limits, which systems must meet by 2029. Federal data can't tell you about your own pipes: lead comes from service lines and plumbing, so test your tap if your home was built before 1986. For the official word, read the utility's annual Consumer Confidence Report.

Does South Granville Water&sewer Authority water have PFAS?

Yes. EPA's 2023–2025 testing of South Granville Water&sewer Authority found 2 PFAS at least once. The highest entry-point averages were above the federal limit for PFOA and PFOS: PFOA 6 ppt, PFOS 10.5 ppt (limit 4 ppt for PFOA and PFOS, 10 ppt for the others).

What is the lead level in South Granville Water&sewer Authority water?

The most recent 90th-percentile lead result for South Granville Water&sewer Authority is 3 ppb, for the period ending Dec 2025. The federal action level is 15 ppb, falling to 10 ppb in November 2027. The 90th percentile means 9 in 10 homes sampled were at or below this number. Individual homes can be higher.

Check these numbers yourself

Every figure on this page comes from public EPA records. You don't have to take our word for it:

Found something that doesn't match? Tell us and we'll check it against EPA's records. How we check our data.